INDUSTRIAL HUMIDITY CONTROL / SINCE 2004 Talk to a specialist 765-702-4083
IHCIndustrial
Humidity Control LLC
COMPONENTS & CONTROLS

Omron PLC Controller

Controller specifications, operating sequence, indicators, and troubleshooting.

Industrial Humidity Control · IHC–TDD–PLC–0926 · Rev A · Updated 2026-11-04

Before service: Isolate power and water and verify zero pressure. Read the safety instructions →

Controller & connections

Identify the controller and the devices it coordinates.

Before inspection or service

ZEN-10C1AR-A-V2 specifications

The pump-station control circuits also use 24 VAC for the humidistat and fan relays. That control signal is not the supply rating of this AC-powered PLC model. Confirm the installed station schematic before testing.

ZEN-10C1AR-A-V2 specifications
ItemSpecification
Power supply100–240 VAC nominal, 85–264 VAC range · 50/60 Hz
Consumption8 VA maximum
Inputs / outputs6 digital inputs and 4 relay outputs; source rating 8 A at 250 VAC / 24 VDC
DisplayBacklit LCD · 12 characters × 4 lines
ProgramLadder logic; timers, counters and comparators
MountingDIN rail or surface · approximately 70 × 90 × 56 mm
Environment0–55°C · 10–90% RH, non-condensing
Other featuresClock/calendar and EEPROM backup

Source reference · page 1 (PDF)

What the PLC controls

What the PLC controls
ComponentRole
Humidistat / cube relay24 VAC humidity call becomes the start input.
Q0 / fansFan relay control; immediate start and delayed stop.
Q1 / pump circuitMotor contactor, inlet solenoid, EDV coil and green RUN indicator.
HPS / Input 1Pressure-proven signal; failure to prove pressure triggers shutdown.
Q2 / red FAULTPressure fault indication.
Q3 / amber MAINT500 pump-hour maintenance reminder; reset after service with buttons 3 + 4.
Hour meterRecords pump run time for maintenance planning.

Source reference · page 5 (PDF)

Sequence & screen display

Read the startup, pressure proof and shutdown stages.

From humidity call to normal operation

Three original PLC screen diagrams show the start signal, fan output and pump-start stages.
PLC screen display during startup. Open image to enlarge ↗
  1. The humidistat calls and the cube-relay LED lights. The start signal remains present while demand continues.
  2. The fans start immediately. The first output square darkens, the orange fan indicator lights and the 10-second pump delay begins.
  3. At the end of the delay, the pump circuit starts, the green RUN indicator lights and the 25-second pressure timer begins.
  4. While waiting for pressure proof, the red indicator is also on. Once pressure is proven, red clears and the pump continues near 1,000 psi.

Source reference · page 2 (PDF)

Fault shutdown and normal shutdown

Failure to prove pressure in time produces a latched red FAULT condition and stops the system. A cube-relay LED can remain lit because the humidistat is still calling; this does not mean the pump is being powered. Correct the pressure problem before cycling the start signal to reset.

During normal shutdown, humidity demand ends, the pump stops and the EDV opens. Fans continue for 10 seconds before stopping.

PLC screen diagrams distinguish the waiting pressure timer, pressure-proven input and latched fault state.
Pressure-build, normal-run and fault screens. Open image to enlarge ↗

Source reference · page 3 (PDF)

Timers & maintenance

Check the two operating delays and reset completed maintenance.

T1 and T2 timer settings

T1 delays pump start after the fans start. T2 delays fan stop after the pump stops. Both are normally 10 seconds. Q0 has no startup delay; Q1 has no shutdown delay.

  1. Press OK, select Parameter using the down arrow, then press OK.
  2. Select the required timer. If necessary, press OK so the timer number blinks, select T1 or T2 with the up/down arrows, and confirm with OK.
  3. Move left to the timer value and press OK. Move between digits with the left arrow; change the value with up/down arrows, then press OK.
  4. Press ESC twice to return to the normal screen. Observe a complete cycle to verify the setting.

Source reference · page 6 (PDF)

500-hour reminder and fault counters

Perform the oil, filter, belt and pump-head checks when the amber maintenance indicator comes on. Then press buttons 3 and 4 together until the amber light goes off. Record the hour-meter reading and completed work.

Press ESC from the normal PLC operating screen to view fault counters. A reset does not repair the condition that caused a fault.

Source reference · page 5 (PDF)

Troubleshooting

Use the indicators to find the affected control or water circuit.

Controller symptoms and checks

Pump will not start

Possible cause
No humidity call, missing start signal or a latched fault.
What to check
Check the set point, cube-relay LED and red FAULT indicator. Correct a fault before resetting.

Red light stays on or system stops after 25 seconds

Possible cause
Pressure is not proven, or the HPS signal is missing.
What to check
Check water supply, filters, leaks and actual gauge pressure; then have a qualified technician verify the HPS connection.

Fans do not start

Possible cause
Missing fan-control signal, remote contactor failure or wiring fault.
What to check
Check the fan-control circuit and relay using the station schematic.

Fans start but pump does not

Possible cause
T1 setting, pump output or pump circuit problem.
What to check
Observe the startup screen and verify T1, Output 1 and the pump contactor circuit.

Pump runs with low pressure or no mist

Possible cause
Inlet valve not opening, restricted supply or a hydraulic fault.
What to check
Check the valve command, inlet water and pressure system.

Nozzles drip after shutdown

Possible cause
EDV is not opening or its drain is restricted.
What to check
Check shutdown pressure and the drain-valve circuit.

Intermittent starting or continuous running

Possible cause
Unstable or stuck humidity call, or loose/shorted control wiring.
What to check
Observe the cube-relay LED and check the humidistat and its connections.

Blank or frozen PLC display

Possible cause
Controller supply or internal fault.
What to check
Have a qualified technician verify the installed PLC’s rated AC supply and fuse protection. Do not confuse its supply with the 24 VAC field-control circuit.

Maintenance reminder will not clear

Possible cause
Reset incomplete or controller setting issue.
What to check
After completing maintenance, press buttons 3 + 4 together; consult IHC if the indicator remains on.

Source reference · page 7 (PDF)

Parts & references

Continue with related guides, parts and the original PDF.

Original & related PDFs

This web guide is adapted from the IHC reference linked below. The original PDF retains its diagrams, document revision and printable layout.

Need help with your system?

Talk through your facility or an existing system with IHC.

Contact IHC