INDUSTRIAL HUMIDITY CONTROL / SINCE 2004 Talk to a specialist 765-702-4083
IHCIndustrial
Humidity Control LLC
COMPONENTS & CONTROLS

Inlet Solenoid Valve

Low-pressure water inlet valves, coil identification, operation, and troubleshooting.

Industrial Humidity Control · IHC–TDD–ISV–1026 · Rev A · Updated 2026-11-04

Before service: Isolate power and water and verify zero pressure. Read the safety instructions →

Identification & supply

Identify the inlet valve and the water supply it controls.

Before inspection or service

The pump’s incoming-water valve

The inlet solenoid is a normally closed, ⅜-inch brass valve after the 5-micron pre-filter and before the high-pressure pump. It opens when PLC Output 1 commands the pump to run, then closes when the pump stops. The main supply valve normally remains on during service operation.

This is a low-pressure inlet component. It is different from the normally open electric drain valve on the high-pressure side.

Source reference · page 1 (PDF)

Parts and supply requirements

Parts and supply requirements
ItemReference specification
93368Inlet valve with 115 V coil for a matching pump station
93596Inlet valve with 230 V coil for a matching pump station
ValveTwo-way, normally closed · ⅜-inch brass body
ControlPLC Output 1 · DIN plug with four-spade connector
Station supply25–100 psi in this station reference; confirm the installed pump’s own inlet-pressure limit
Available flowContinuous, uninterrupted supply of at least 1.5 times the station’s rated pump capacity
Water pathWater treatment → 5-micron pre-filter 92608 → inlet solenoid → pump

Source reference · page 1 (PDF)

Identify the components

Diagram identifies the coil retaining nut, solenoid coil, DIN connector, diaphragm cover, brass body and threaded port; arrows show treated water entering through the filter before the pump.
Inlet valve components and water path. Open image to enlarge ↗
  • The retaining nut holds the coil on the stem.
  • The coil moves the internal piston; normal operation produces an audible or tactile click.
  • The diaphragm controls flow. Observe the body’s flow-direction marking when replacing the valve.
  • The source recommends keeping a spare matched coil and DIN plug.

Source reference · page 2 (PDF)

Sequence & electrical integration

Understand how the inlet valve follows the pump command.

Operating sequence

Operating sequence
StageValve state
No humidity demandDe-energized and closed; pump off.
Fan lead, first 10 secondsFans run; valve remains closed.
Pump startsOutput 1 energizes the coil, EDV circuit, motor contactor and green RUN light; inlet valve opens.
Pressure provingPLC waits for the HPS signal during its 25-second pressure timer.
Demand endsPump stops and inlet coil de-energizes immediately; valve closes.
Fan run-onFans run 10 more seconds; valve stays closed.

Source reference · page 3 (PDF)

Coil voltage and shared output

The inlet coil shares Output 1 with the EDV coil, motor-start contactor and green RUN indicator. The coil voltage must match the station supply and installed wiring. Do not assume every station uses the same coil.

Electrical measurements on an energized station are for qualified personnel. No voltage during a pump command points toward the wiring or PLC output; correct voltage with no movement points toward the coil or valve.

Simplified circuit shows the inlet valve, electric drain valve, motor contactor and green indicator connected to PLC Output 1.
Output 1 circuit and supply requirements. Open image to enlarge ↗

Source reference · page 4 (PDF)

Inspection & replacement

Check the connector, coil and diaphragm before selecting replacement parts.

Inspection procedure

  1. Stop and isolate the system, shut off the water supply, and verify zero pressure.
  2. Inspect the DIN connector for loose terminals, damage, moisture or corrosion. Clean carbon from the connector contacts and replace a damaged plug.
  3. Remove the retaining nut and lift the isolated coil straight off the stem. Bulging, burns, melted plastic or water intrusion are reasons to replace it with the correct voltage model.
  4. If water passes when the valve is off, or flow remains restricted when it is on, inspect for scale or a damaged diaphragm. The IHC guide recommends complete valve-body replacement rather than diaphragm repair.
  5. Reassemble, secure all connections and guards, restore water, then perform a controlled operating cycle. Confirm opening only on a pump command, pressure recovery and closing at shutdown.

Source reference · page 5 (PDF)

Symptoms and checks

Clicking but no water flow

Possible cause
Debris, scale or a damaged diaphragm.
What to check
Inspect the isolated valve; replace the complete body and check water treatment.

No click when commanded to run

Possible cause
Failed coil, bad DIN connection or missing PLC output.
What to check
Check connector condition and correct coil voltage; have a qualified technician test Output 1.

Intermittent flow or erratic pump pressure

Possible cause
Loose DIN plug, unstable voltage or a failing coil.
What to check
Inspect and secure connections with power isolated; check voltage and coil condition.

Low inlet pressure or cavitation

Possible cause
Blocked filter, restricted supply or a scaled valve.
What to check
Replace filter 92608 as needed, check treatment and supply flow, and clean or replace the valve.

Water flows after the pump stops

Possible cause
Valve stuck open or torn diaphragm.
What to check
Replace the complete valve body.

Slow pressure build or red FAULT light

Possible cause
Insufficient water through the inlet path or a leak.
What to check
Check the inlet gauge, filter, valve and distribution lines before resetting the fault.

Source reference · page 6 (PDF)

Parts & references

Continue with related guides, parts and the original PDF.

Original & related PDFs

This web guide is adapted from the IHC reference linked below. The original PDF retains its diagrams, document revision and printable layout.

Need help with your system?

Talk through your facility or an existing system with IHC.

Contact IHC