FanMist Master Glossary

A searchable field glossary covering equipment, tubing, controls, water, maintenance, load calculations and industry terms.

Industrial Humidity Control · IHC–FMG–001 · Master glossary v2 · Updated 2026-11-04

Equipment & installation

Acronyms, system components, tubing, fittings and mounting terms.

How to use this reference

Browse by category or search the Resources library for a term or part number. The web glossary brings the source entries into readable tables; the original PDF remains available below.

Definitions help identify concepts and components. Use the linked equipment and service guides for model-specific ratings and procedures. Standards named here are references, not a claim of equipment certification.

Source reference · page 1 (PDF)

Acronyms & abbreviations

Acronyms & abbreviations
AbbreviationMeaning
ACHAir changes / exchanges per hour
ANSIAmerican National Standards Institute
ANSI/HIANSI / Hydraulic Institute
APSAutomated pump station
ASHRAEAmerican Society of Heating, Refrigerating and Air-Conditioning Engineers
ASMEAmerican Society of Mechanical Engineers
BAS/EMSBuilding automation / energy management system
CFMCubic feet per minute
EDVElectric drain valve
EMCEquilibrium moisture content
EREvaporation ratio: CFM per lb/hr of water output
ESDElectrostatic discharge
ExAExhaust airflow
FNPTFemale National Pipe Thread
FSCFinal system capacity
GDGrains difference, grains/ft³
GHTGarden hose thread
GPMGallons per minute
HPHorsepower
HPSHigh-pressure safety switch
HRO20Neptronic humidistat model
HVACHeating, ventilation and air conditioning
IDInside diameter
ISOInternational Organization for Standardization
LOTOLockout/tagout
MAUMakeup-air unit
MNPTMale National Pipe Thread
MSDMoisture-sensitive device
MuAMakeup airflow
NECNational Electrical Code
NFPANational Fire Protection Association
NPTNational Pipe Thread
ODOutside diameter
OSHAOccupational Safety and Health Administration
PLCProgrammable logic controller
PPEPersonal protective equipment
PSIPounds per square inch
RHRelative humidity
ROReverse osmosis
ROIReturn on investment
RTORegenerative thermal oxidizer
RTURooftop unit
SSStainless steel
TABTest and balance
TDSTotal dissolved solids
TMCTarget moisture content
ULUL / Underwriters Laboratories
UNCUnified National Coarse thread
VACVolts alternating current
VOCVolatile organic compound

Source reference · page 2 (PDF)

System & equipment components

System & equipment components
TermMeaning
Pump StationThe enclosed equipment package housing the pump, PLC controller, and associated safety/control devices that generates and regulates 1000-psi water for the system.
PLC ControllerThe programmable logic controller (Omron) inside the pump station that manages pump/fan sequencing, timers, and safety shutdowns.
Electric Drain Valve (EDV)A Danfoss 2/2-way, normally-open solenoid valve on the pump discharge manifold that releases line pressure on shutdown to mechanically close the nozzles.
High-Pressure Safety Switch (HPS)Pressure-proof switch used by the PLC to shut the pump down when pressure is not established or is lost. The black switch reference lists a nominal 580 psi activation; the sequence describes proving approximately 550 psi within the configured interval.
Unloader ValveRegulates approximately 1,000 psi discharge pressure and returns pump bypass capacity to the inlet. Excessive bypass can heat the returned water; use the current unloader guide to evaluate sizing and thermal relief.
Thermal Relief ValveOpens automatically if water temperature inside the pump exceeds 145°F.
Low-Pressure Inlet Solenoid ValveMaintains proper water volume and pressure into the pump from the incoming supply; functions as an automated, normally-closed "smart faucet" for the pump's low-pressure inlet side.
24 VAC TransformerSupplies low-voltage power for the humidistat and fan control circuits.
Fan Manual Override Toggle SwitchAllows independent testing of fan rotation from the pump station without a humidistat call.
HumidistatWall-mounted RH sensor/controller (Neptronic HRO20) that sends the start/stop signal driving the PLC's pump and fan cycling.
Mist-RingA stainless-steel ring carrying the nozzle ports, mounted to the face of each fan to distribute atomized water evenly into the airstream.
NozzleA stainless-steel, ruby-orifice atomizing tip threaded into a Mist-Ring port; mechanically opens and closes at a set cracking pressure.
Ball Valve AssemblyThe fitting assembly connecting a fan's drop-down tube to its Mist-Ring, allowing that fan to be isolated for flushing or service.
Fan Contactor Relay BoxA remote junction box containing a contactor that switches plant power to a fan on the low-voltage signal from the pump station.
Bladder (Expansion) TankA pressurized reclaim tank that can capture the EDV's drain release back into the pump's low-pressure water supply instead of sending it to waste.
Diaphragm (Solenoid Valve)The internal rubber component inside a water inlet solenoid valve that controls flow; if torn, out of position, or scaled, the valve will allow flow when off or restrict flow when on. Replacing the whole valve body is recommended over repairing the diaphragm alone.

Source reference · page 3 (PDF)

Tubing, fittings & hardware

Tubing, fittings & hardware
TermMeaning
High-Pressure TubeBlack nylon (Polyamide 12) tubing rated for 1000- psi operation, used in 1/2" and 3/8" sizes throughout the system.
Slip-Lok FittingA push-to-connect fitting system for high-pressure nylon tubing; tool-free to install and service.
Slip-Lok CouplingA fitting that joins two lengths of same-diameter tubing to extend a run.
Slip-Lok 90° ElbowA fitting that changes tubing direction 90°; used sparingly in favor of bending the tube itself.
Slip-Lok Three-Way TeeA fitting that splits or combines flow, such as branching off to a drop-down line.
Transition FittingA Slip-Lok x NPT adapter that steps a run down from 1/2" to 3/8" tubing as it branches toward the fans.
Primary O-ringThe oversized internal O-ring inside a Slip-Lok fitting that compresses against the tube to form the leak-proof seal.
Backup Urethane O-ringAn optional secondary O-ring that buffers the ferrule teeth from the primary O-ring, extending fitting life.
FerruleThe internal locking element inside a Slip-Lok collar that grips the tube once it is inserted and tugged back.
Drop-Down TubeThe 3/8" tube run connecting the ceiling-routed high-pressure line down to each fan's ball valve assembly.
Wall ClampA vinyl-coated steel clamp used to secure tubing to walls or structural supports.
Plumber's TapeThread-sealing tape applied to every threaded (NPT) connection in the system.
Compression FittingA stainless steel or brass fitting that connects rigid tube (typically stainless steel pipe) without welding or soldering; a nut and ferrule compress around the tube to create a leak-resistant seal.
Bulkhead FittingA fitting designed to pass through a panel or wall connection point (e.g. drain bypass on older pump stations), rather than joining two lengths of tube in-line.

Source reference · page 4 (PDF)

Installation & mounting terms

Installation & mounting terms
TermMeaning
Moisture PlumeThe region of atomized mist projected into the air by a fan. The reference layout allows approximately 4 feet in diameter by 22 feet of unobstructed travel; actual evaporation depends on airflow, nozzle output and room conditions.
Fan BracketThe mounting hardware that attaches a fan to structural steel, angle iron, or a wall.
Angle IronStructural steel used as a ceiling-truss mounting point for fan brackets.
Ceiling-Hung MountingMethod of suspending a fan from ceiling truss angle iron rather than a wall or column.
Drip LoopA deliberate downward loop in fan supply wiring that directs accumulated condensation away from the motor housing.
Local Disconnect SwitchA dedicated on/off switch installed at each fan for independent maintenance control.
Coil MemoryThe tendency of coiled nylon tubing to retain its rolled shape; relaxed by uncoiling and warming before routing.
DeburrLightly filing or sanding a freshly cut tube end smooth before inserting it into a fitting.
180° SweepA flexible bend formed in the drop-down tube that allows a straight connection into the ball valve assembly.
Daisy-Chain OrderThe fan-by-fan installation or flushing sequence, proceeding outward from the pump station.

Source reference · page 5 (PDF)

Controls, operation & care

Electrical terminology, operating parameters, water quality and maintenance.

Electrical & controls terminology

Electrical & controls terminology
TermMeaning
Fan/Pump DelayPLC-controlled sequencing: fans start 10 seconds before the pump; on shutdown, fans continue running 10 seconds after the pump stops.
Pressure-Build TimerThe PLC's timed window — 25 seconds in normal operation, 60 seconds on initial startup — for the pump to reach 550 psi before faulting off.
Strain ReliefA fitting at a pump-enclosure cable entry point that protects wiring from mechanical stress.
Normally Open (NO)A valve or relay-contact state when not energized. For the EDV, normally open means water can discharge when coil power is off; energizing the coil closes the drain.
Terminal Block (TB1)The humidistat's internal wiring strip; only 3 of its 16 positions (Common, 24VAC, Humidify Output) are actually used.
SetpointThe target RH% programmed into the humidistat that determines when the system cycles on and off.
Dead BandThe gap between the RH that starts the system and the RH that stops it; a wider setting reduces cycling frequency.
Proportional BandThe RH range over which the humidistat modulates its control response.

Source reference · page 6 (PDF)

Operating parameters & specifications

Operating parameters & specifications
TermMeaning
System Operating PressureThe normal FanMist high-pressure operating setting, approximately 1,000 psi. Manufacturer maximum component ratings are not alternate station operating settings.
Cracking PressureThe 300-psi threshold at which a nozzle's internal spring mechanically opens to atomize water.
Burst RatingA component failure-pressure rating, distinct from its allowable operating pressure. The source lists 2,500–2,800 psi for its tubing; the system operates at approximately 1,000 psi.
Evaporation Rate (ER)The FanMist sizing ratio of fan airflow in CFM to water output in lb/hr. The installation handbook cites 80 or higher; the nozzle and load references cite greater than 75. Use actual fan and nozzle ratings for the calculation.
Operating CycleA recurring humidity call followed by a satisfied period. The reference uses ten minutes on and ten minutes off as a typical illustration; actual cycling depends on demand and controls.
Average Seasonal RuntimeTypical annual operating hours — 1,500–2,000 — during the humidification season (Oct 15–Apr 15).

Source reference · page 7 (PDF)

Water treatment & quality terms

Water treatment & quality terms
TermMeaning
Pre-FilterA 5-micron cartridge filter on the incoming water line that protects the pump and nozzles from particulate.
ScalingMineral deposits on wetted surfaces. Treatment depends on the water analysis; softening and scale-control systems address scale differently and do not necessarily remove dissolved minerals.
Air DustingAirborne residue left when water containing dissolved minerals evaporates. RO reduces dissolved minerals; hardness control alone does not eliminate all dissolved solids.
Water SoftenerEquipment that reduces water hardness to prevent scaling.
Reverse Osmosis (RO)A water treatment method that removes dissolved minerals to prevent air dusting.

Source reference · page 8 (PDF)

Procedures & maintenance terms

Procedures & maintenance terms
TermMeaning
Lockout/Tagout (LOTO)OSHA 1910.147 procedure for isolating hazardous energy sources before servicing equipment.
Flushing ProcedureMandatory pre-startup step that runs water through the system, nozzles removed, to clear installation debris before nozzles are installed.
System StartupThe sequenced procedure for bringing the system online and confirming correct pump, fan, and pressure operation.
Pre-Start Fan TestingVerifying correct fan rotation using the manual override switch, both before and after final wiring.
Warranty ClaimThe formal process for requesting repair or replacement of a defective component under the manufacturer's warranty terms.

Source reference · page 9 (PDF)

Physics & load calculation

Scientific principles and the terms used in sizing worksheets.

Physical & scientific principles

Physical & scientific principles
TermMeaning
Dalton’s Law & the Ideal Gas LawDalton’s law describes each gas’s contribution to total pressure, including water vapor. The ideal-gas approximation supports many air and vapor calculations. Air movement and mixing distribute moisture through a space.
Fick's Laws of DiffusionDescribe diffusion down a concentration gradient. They do not assign water vapor a universal travel speed; bulk fan airflow and turbulent mixing also affect distribution.
Clausius-Clapeyron EquationDescribes how saturation vapor pressure changes with temperature. Warmer conditions require more water vapor to reach the same RH; the rate of change depends on temperature.

Source reference · page 10 (PDF)

Load calculation & psychrometric terms

Load calculation & psychrometric terms
TermMeaning
Governing AirflowThe single most important input for a load calculation: the greater of total exhaust CFM or total makeup-air CFM (or an estimated ACH when CFM data isn't available). Whichever is larger drives the load calculation.
Air BalanceThe relationship between a building's exhaust-air CFM and makeup-air CFM; determines how much of the building's air exchange is deliberate (ventilation) versus incidental (infiltration).
VentilationThe deliberate, engineered exchange of air with the outdoors — process exhaust systems pulling air out, makeup-air units/economizers/supply fans bringing tempered air back in. Measured and usually preconditioned.
InfiltrationThe uncontrolled counterpart to ventilation: outdoor air leaking in through door gaps, dock doors, wall penetrations, and envelope imperfections, filling whatever gap a building's air balance leaves.
Negative Pressure (Building)Condition where exhaust CFM exceeds makeup-air CFM; the building pulls more air out than it replaces, drawing the shortfall in through infiltration. In this case exhaust CFM is the more representative governing figure.
Positive Pressure (Building)Condition where makeup-air CFM exceeds exhaust CFM; more air is pushed in than removed, suppressing infiltration (sometimes at the cost of excess conditioning capacity).
Balanced Pressure (Building)Condition where exhaust and makeup-air CFM are approximately equal; infiltration is minimal and measured makeup-air CFM is a trustworthy load input.
Grains/ft3 DifferenceTarget indoor water-vapor content minus the outdoor-air moisture allowance, expressed in grains per cubic foot. The guide’s 50% factor is a conservative outdoor-moisture assumption, not moisture lost simply by heating air.
LoadThe total amount of moisture, in pounds of water vapor per hour, that the FanMist system must add to bring incoming air up to the target RH under design winter conditions. The central concept of the Load Calculator Guides.
Final System CapacityLoad plus a 15% safety margin (baseline; higher- throughput or tighter-tolerance facilities may reasonably size larger), accounting for colder-than- design temperatures and minor operating variation.
Psychrometric Saturation TableReference table (Table 2-A in each guide) showing grains of water vapor per cubic foot of air at 100% saturation for a given temperature; the basis for all load-calculation moisture lookups. Key conversion: 7,000 grains = 1 lb of water.
Target Moisture Content (TMC)The grains/ft3 value at target indoor RH% and temperature (saturation grains/ft3 × desired RH%).
Grains Difference (GD)The moisture deficit in grains per cubic foot used in the practical load formula. Calculate from the indoor target and the chosen outdoor-moisture allowance.
Formula #1 (CFM Basis)The preferred practical sizing method: Load (lbs/hr) = Grains/ft3 Difference × (Governing CFM × 60) ÷ 7,000 grains/lb. Used when exhaust/makeup-air CFM data is known.
Formula #2 (ACH Basis)Alternate practical sizing method used when CFM data isn't available: Load (lbs/hr) = Grains/ft3 Difference × (Total Volume ft3 × ACH) ÷ 7,000 grains/lb.
Practical MethodThe reference’s initial sizing approach: replacement-air volume multiplied by moisture deficit, followed by an explicit capacity margin. Secondary product, process and occupancy effects require separate evaluation when material.
Comprehensive MethodSizing method that builds on the Practical Method by adding secondary load factors (Product Regain, Process Vapors, People) for more precise calculations — used for high-throughput facilities or tight tolerance targets.
Product RegainSecondary load factor (moisture sink, increases load): dry incoming stock (lumber, paper rolls, PCBs/components) absorbs moisture from shop air as it reaches equilibrium, requiring additional humidifier output.
Process VaporsSecondary load factor (moisture gain, decreases load): water vapor released by certain operations (finishing/spray booths, glue curing, ink/coating drying, aqueous cleaning) partially offsets the humidification need.
EconomizerHVAC controls that vary outdoor-air intake. Use actual winter outdoor-air settings and design airflow when estimating makeup air; a damper percentage is not a universal ventilation requirement.
Freeze-Protection LockoutA low-temperature control sequence that can change HVAC operation. Confirm the actual unit’s winter outdoor-air delivery from its design and controls before using it in a load calculation.

Source reference · page 11 (PDF)

Processes & references

Industry-specific concepts and standards named in the source.

Industry-specific process terms

Industry-specific process terms
TermMeaning
HygroscopicA material that exchanges moisture with its surroundings as it approaches equilibrium. Wood and paper are common examples.
Web BreakA tear or break in a moving paper web; moisture variation, tension and static are among possible contributing factors.
Static Electricity (Paper/Print)Charge produced during contact and separation at rollers and guides. Humidity can affect surface conductivity and charge dissipation, alongside other process controls.
Electrostatic Discharge (ESD)A discharge that can damage sensitive electronics. Humidity control complements grounding, ionization and ESD-safe handling; it does not replace them.
Moisture-Sensitive Device (MSD)An electronic package with specified moisture-exposure and storage requirements. Follow its manufacturer and the applicable handling procedures.
Floor LifeThe permitted exposure time of a moisture-sensitive device under its specified conditions after removal from protective packaging.
Triboelectric ChargeCharge generated by materials contacting and separating, including handling, conveyors and packaging. Humidity can affect how quickly it dissipates.
ISO Cleanroom ClassificationA classification of airborne particle cleanliness. Use the room’s actual mechanical and process design when evaluating humidity and outdoor-air load.
ANSI/ESD S20.20An ESD-control-program standard referenced by the electronics guide; a room humidity target alone does not establish program compliance.
Fully Exhausted Process StreamProcess air discharged outdoors rather than returned to the served space. Count the actual outdoor discharge in the air balance.
Recirculating ExhaustA process extraction system that returns some appropriately treated air indoors. Count the portion actually lost outdoors and verify any assumed loss fraction.
Regenerative Thermal Oxidizer (RTO)Equipment used to treat certain process exhaust streams. Confirm its actual operating airflow when estimating the plant’s outdoor exhaust.

Source reference · page 13 (PDF)

Standards & referenced codes

Standards & referenced codes
TermMeaning
NEC / NFPA 70Electrical installation code referenced by the source. The applicable edition and local requirements are determined for the installation.
OSHA 1910.147Hazardous-energy control / lockout-tagout reference named in the source.
OSHA 1910.132Personal protective equipment reference named in the source.
ASME B31.3Process-piping code referenced in the source; its mention does not establish certification or project-specific applicability.
ANSI/HI 1.6Hydraulic Institute pump standard referenced in the source. Confirm the correct applicable standard with the equipment manufacturer.
ASHRAE 188Legionellosis risk-management standard referenced in the source. Scale control and RO do not by themselves establish a complete water-management program.
ASHRAE 62.1Ventilation for acceptable indoor air quality standard referenced in the source. Confirm project-specific ventilation requirements with the mechanical design team.
ANSI Z535Safety-color, sign and labeling standards referenced in the source.
UL 508AIndustrial-control-panel standard referenced in the source. A glossary reference is not a statement that a particular panel is listed or certified.

Source reference · page 14 (PDF)

Parts & references

Continue with related guides, parts and the original PDF.

Original & related PDFs

This web guide is adapted from the IHC reference linked below. The original PDF retains its diagrams, document revision and printable layout.